Knowledge! Cleanroom Classification (Class A, B, C, D)

Posted on 2024-04-10


GMP Cleanliness Class A,B,C,D Main Parameter Requirement

Class A clean area
 
The air temperature in the clean operation area should be 20℃-24℃.

The relative humidity of the air in the clean operation area should be 45%-60%.

Air velocity in the operation area: horizontal air velocity ≥ 0.54m/s; vertical air velocity ≥ 0.36m/s

Leakage test of high efficiency filter is more than 99.97%

Illumination: >300lx-600lx

Noise: ≤75db (dynamic test)

Class B clean area
 
The air temperature in the clean operation area should be 20℃-24℃.

The relative humidity of the air in the clean operation area should be 45%-60%.

Room ventilation times: ≥ 25 times / h
 
Differential pressure: B-level area relative to the outdoor ≥ 10Pa, different areas of the same level
according to the direction of air flow should maintain a certain pressure difference.

Leakage check of high efficiency filter is more than 99.97%.

Illumination: >300lx-600lx

Noise: ≤75db (dynamic test)

Class C clean area
 
The air temperature in the clean operation area should be 20℃-24℃.

The relative humidity of the air in the clean operation area should be 45%-60%.

Room ventilation times: ≥ 25 times / h

Differential pressure: C-level area relative to the outdoor ≥ 10Pa, different areas of the same level
according to the direction of air flow should maintain a certain pressure difference.

Leakage check of high efficiency filter is more than 99.97%.
 
Illumination: >300lx-600lx

Noise: ≤75db (dynamic test)
 
Class D clean area
 
The air temperature in the clean operation area should be 18°C-26°C.

The relative humidity of the air in the clean operation area should be 45%-60%.

The number of room ventilation: ≥ 15 times / h
 
Differential pressure: 100. 000 level area relative to the outdoor ≥ 10Pa
 
Leakage detection of high-efficiency filters is greater than 99.97
 
Illumination: >300l×-600lx
 
Noise: ≤75db (dynamic test)

GMP workshop ABCD clean grade standard table reference:

cleanness
level
Maximum permissible number of suspended particles/m³
Approximate
correspondence
to conventional
specifications
Static
Dynamic
≥0.5μm
≥5μm
≥0.5μm
≥5μm
Grade A
3520(ISO5) 20
3520(ISO5)
20
Level 100
Grade B
3520(ISO5)
29
352000(ISO7)
 
2900
Level 100
Grade C
352000(ISO7)
2900
3520000(ISO8)
 
29000
Level 10,000
Grade D
3520000(ISO8)
29000
not regulated
not
regulated
Level 10,0000

Comparison of the 1998 and 2010 editions of the GMP clean area standards for airborne particles
at all levels:

cleanness level
GMP 2010
Equivalent to ISO
standards
 
GMP 1998
Equivalent to ISO standards
A
Dynamic ISO5
Level 100
ISO5
Static ISO5
B
Dynamic ISO7
   
Static ISO5
C
Dynamic ISO8
Level 10000
ISO7
Static ISO7
D
Dynamic ISO7
10000 Levels
ISO8
Static ISO8

The air cleanliness of a pharmaceutical production clean room
(area) is divided into four levels:

Clean room (area) air cleanliness level table
 
Cleanliness level
Maximum permissible number of
dust particles/cubic meter ≥
0.5μm number of dust particles
0.5μm number of dust particles Number of 5μm
dust particles
Maximum permissible number of microorganisms planktonic bacteria/m³
Sedimentation
bacteria/dish
Class 100
3,500
0 5 1
Class 10,000
350,000
2,000
100 3
Class 100,000
3,500,000
20,000
500 10
Class 300,000
10,500,000
60,000
1000 15


ISO 14644-1 (international standard)

Air cleanliness
class (N)
Maximum concentration limit for particles larger than or equal to the indicated particle size
(pcs/cubic meter of airborne particles)
0.1μm
0.2μm
0.3μm
0.5μm
1.0μm
5.0μm
ISO Class1
10 2        
ISO Class2
100 24 10 4
ISO Class3
1,000 237 102 35 8
ISO Class4
10,000 2,3700 1,020 352 83
ISO Class5
100,000 23,700 10,200
3,520
832 29
ISO Class6
1,000,000 237,000 102,000
35,200
8,320
293
ISO Class7
     
352,000
83,200
2,930
ISO Class8
     
3,520,000
832,000
29,300
ISO Class9
      35,200,000
8,320,000
293,000
Note: Due to the uncertainties involved in the measurement process, no more than three valid concentration figures are required to determine the level of the class.



Airborne Particle Cleanliness Classes for Cleanrooms and Clean Zones

Air Cleanliness Class
Maximum concentration limitsfor particle sizes greater than or equal to those in the table (pc/m)
0.1μm
0.2μm
0.3μm
0.5μm
1.μm
5μm
1 10 2        
2 100 24 10 4    
3 1000 237 102 35 8  
4 (tenth grade) 10000 2370 1020 352 83  
5(Hundred levels) 100000 23700 10200 3520 832 29
6(Thousand levels) 1000000 237000 102000 35200 8320 293
7(Ten thousand
levels)
      352000 83200 2930
8(One hundred
thousand level)
      3520000 832000 29300
9(One million level)
      35200000 8320000 293000

Approximate Comparison of Cleanliness Levels by Country

pcs/ M
 
≥0.5μm
ISO
 
14644-1(1999)
US
 
209E(1992)
US
 
209D(1988)
EEC
 
cGMP(1989)
FRANCE
 
AFNOR(1981)
GERMANY
VDI
 
2083(1990)
JAPAN
 
JAOA(1989)
1              
3.5 2         0 2
10.0  
M1
         
35.5 3 M1.5 1     1 3
100   M2          
353 4 M2.5 10     2 4
1,000   M3          
3,530
5 M3.5
100
A+B
4,000
3 5
10,000
  M4          
35,300
6 M4.5
1,000
1,000   4 6
100,000
  M5          
353,000
7 M5.5
10,000
C
400,000
5 7
1,000,000
  M6          
3,530,000
8 M6.5
 
100,000
D
4,000,000
6 8
10,000,000
  M7          

Cleanroom Classes and AHU Filter Matches

 
For cleanroom class A, air handling units should be selected with a high efficiency filter (HEPA) rating of H13 or above to ensure that the filtration effect meets the requirements.

For Cleanroom Class B, the air handling unit should be selected with a high efficiency filter (HEPA) rating of H14 or higher to provide higher filtration and better air quality control. For Cleanroom Class C, air handling units should be selected with a combination of a primary filter (G4 or F5 rating) and a high efficiency filter (HEPA) rating of H14 or higher to ensure higher filtration effectiveness and proper air quality.

For cleanroom class D, air handling units should be selected with a combination of a primary filter (G4 or F5 rating) and a high efficiency filter (HEPA) rating of H15.



Cleanroom class ABCD corresponds to different air handling unit filter specifications and performance
requirements. The following are the requirements for each class:

Class A cleanroom: the filter of air handling unit should be class H14. Class H14 filter can effectively filter 99.995% of 0.3 micron particles, and has high filtration efficiency and trapping capacity.

Class B cleanroom: the filter grade of air handling unit should be H13. H13 filter can effectively filter 99.95% of 0.3 micron particles, and has high filtration efficiency and capture capacity.

Class C cleanroom: the filter of air handling unit should be class H11. Class H11 filter can effectively filter 95% of 0.3 micron particles, and has high filtration efficiency and trapping capacity.

Class D clean room: the filter grade of the air handling unit should be H9. H9 filter can effectively filter 85% of 0.3 micron particles, and has high filtration efficiency and trapping capacity

Hot News
  • DECENT MACHINERY Deepens Overseas Mining Cooperation with High-standard Customized Fan Solutions 2026-09-09 DECENT MACHINERY Deepens Overseas Mining Cooperation with High-standard Customized Fan Solutions Upholding the philosophy of quality-oriented development and customer-centric service, DECENT MACHINERY continues to expand its global mining equipment market footprint. Recently, the company has achieved in-depth and repeated cooperation with a high-standard mining client in Southeast Asia, relying on reliable product quality, rigorous safety standards and transparent full-cycle service, further ...
  • DECENT MACHINERY Delivers Custom‑Built Tunnel Fans for Leading Underground Gold Mine Project in Cent... 2026-09-08 DECENT MACHINERY Delivers Custom‑Built Tunnel Fans for Leading Underground Gold Mine Project in Central Asia DECENT MACHINERY continues to deliver robust custom‑tailored tunnel ventilation solutions for a flagship underground gold mining operation across Central Asia, addressing extreme underground operational challenges within complex deep‑mine environments. The region’s premier underground gold mine has long grappled with persistent operational bottlenecks stemming from narrow underground drifts, kilom...
  • DECENT MACHINERY Deepens European Strategic Cooperation After 3 Years of Dedicated Communication 2026-09-07 DECENT MACHINERY Deepens European Strategic Cooperation After 3 Years of Dedicated Communication Recently, DECENT MACHINERY’s overseas business team held an in-depth face-to-face business meeting and friendly dinner negotiation with long-term European clients in Shanghai. Both parties reviewed the whole progress of project communication, confirmed the official cooperation order, and conducted in-depth discussions on future multi-dimensional strategic cooperation.   The project cooperation bet...
  • New Order Secured: Multistage Centrifugal Fans for a Key Southeast Asia Project 2026-09-04 New Order Secured: Multistage Centrifugal Fans for a Key Southeast Asia Project We are delighted to announce that Decent Machinery has won a new contract for multistage centrifugal fans. This equipment will be deployed in a major China‑aided landmark project in Southeast Asia.   The end customer is a global leading manufacturer of power semiconductors. The multistage centrifugal fans are designed for the factory’s wastewater treatment system, serving as core aeration equipmen...
Category
Get in Touch