I. Definition, Applicable Area, Classification, and Working Principle of Air Conditioners
1. Definition of Air Conditioners: The full name of an air conditioner is a room air conditioner. It is a device that directly provides treated air to a room or other enclosed area, capable of adjusting indoor temperature and humidity.
2. Applicable Area of Air Conditioners:
|
Horsepower (HP) |
Power (W) |
Suitable Area (sqm) |
|
1.0 HP |
2300W—2500W |
11—17 sqm |
|
1.25 HP |
2600W—2800W |
18—23 sqm |
|
1.5 HP |
3000W—3600W |
18—25 sqm |
|
2.0 HP |
4000W—5200W |
30—35 sqm |
|
2.5 HP |
5800W—6200W |
35—45 sqm |
|
3.0 HP |
6500W—7200W |
40—50 sqm |
|
5.0 HP |
12000W |
~60 sqm |
|
10 HP |
24000W |
80—100 sqm |
Calculation Formula: Room area (square meters) × output power per square meter (120-150W) = actual cooling output power required for the room.
3. Power Consumption of Air Conditioners:
|
Horsepower (HP) |
Power (W) |
|
1.0 HP |
880W—950W |
|
1.25 HP |
950W—1300W |
|
1.5 HP |
Around 1300W |
|
2.0 HP |
1800W |
|
3.0 HP |
2800W |
|
5.0 HP |
Around 5000W |
|
10 HP |
Around 10000W |
4. Typical Operating Environment for Air Conditioners:
- Cooling only: 18°C~~43°C;
- Heating and cooling: -5°C—43°C.
5. Classification of Air Conditioners:
- Floor-standing (Cabinet) Air Conditioners: Generally used in living rooms because they have a longer airflow distance.
- Wall-mounted Air Conditioners**: Suitable for family use.
- Window Air Conditioners: Typically used in bedrooms since bedrooms are usually smaller, but window air conditioners have largely been replaced by wall-mounted units.
- Ceiling Air Conditioners and Central Air Conditioners: Typically used in hotels and other establishments with multiple rooms.
- Car Air Conditioners: Used in vehicles to provide convenience to drivers and passengers.
6. Differences Between Inverter and Non-inverter Air Conditioners:
- Inverter Air Conditioners: Start with high power, quickly reach the set temperature, then maintain it with low power, resulting in fast cooling/heating, energy savings, and small temperature fluctuations.
- Non-inverter Air Conditioners: Operate at fixed power, maintaining indoor temperature by frequently turning on and off, which results in slower cooling/heating, a larger impact on the home power grid, and larger temperature fluctuations.
7. Differences Between DC Inverter and AC Inverter Air Conditioners:
- DC Inverter Air Conditioners: Change the power supply voltage to the compressor, thereby altering the compressor's operating speed. The supply voltage ranges from 150V to 260V.
- AC Inverter Air Conditioners: Change the power supply frequency to the compressor, thereby altering the compressor's operating speed. The supply frequency ranges from 10Hz to 150Hz.
8. Cooling Cycle Components:
- Comprised of a compressor, throttling capillary tube, evaporator, condenser, electromagnetic conversion valve, one-way valve, pressure limiter, filter, dryer, silencer, and other components forming a closed system. Refrigerant is charged into the system.
9. Air Circulation Components:
- Composed of a cross-flow fan, centrifugal fan, axial fan, intake air filter, and exhaust grille.
10. Electrical Control Components:
- Consist of a computer control board, temperature display, switch controller, power relay, start relay, overload relay, defrosting relay, thermistor, and other components such as capacitors and compressor heaters.
11. Housing Components:
- Made up of plastic housing for the indoor unit and sheet metal housing for the outdoor unit.
12. Air Conditioner Fans:
- Axial Fan: Used in outdoor units. It generates force through the high-speed rotation of blades, expelling air to facilitate gas exchange with the indoor unit.
- Cross-flow Fan: Used in indoor wall-mounted units. When the fan is in operation, airflow enters the cross-flow fan wheel from one side along the direction perpendicular to the fan axis and exits from the other side.
13. Air Conditioner Performance Coefficient and Energy Efficiency Ratio:
- National Standards for Testing Nominal Cooling Capacity: Indoor dry bulb temperature at 27°C, wet bulb temperature at 19.5°C; outdoor dry bulb temperature at 35°C, wet bulb temperature at 24°C.
- National Standards for Testing Nominal Heating Capacity: Indoor dry bulb temperature at 20°C, wet bulb temperature at 15°C; outdoor dry bulb temperature at 7°C, wet bulb temperature at 6°C.
- (National standards also allow actual cooling/heating capacity to be up to 8% lower than nominal values.)
14. Air Conditioner Performance Coefficient (EER):
- Refers to the ratio of cooling capacity to total power consumption during cooling operation:
EER = Actual Cooling Capacity / Actual Power Consumption (W / W) = Nominal Cooling Capacity / Nominal Input Power (W / W).
- The physical significance of the performance coefficient is that it indicates the amount of cooling generated per watt of electricity consumed. Therefore, the higher the performance coefficient of an air conditioner, the less electricity is consumed to produce the same amount of cooling.
15. Air Conditioner Energy Efficiency Ratio (COP):
- Refers to the ratio of heating capacity to total power consumption during heating operation:
COP = Actual Heating Capacity / Actual Power Consumption (W / W) = Nominal Heating Capacity / Nominal Input Power (W / W).
- The physical significance of the energy efficiency ratio is that it indicates the amount of heating generated per watt of electricity consumed. Therefore, the higher the energy efficiency ratio of an air conditioner, the more energy-efficient it is in producing the same amount of heat.
II. Selection, Installation, and Routine Maintenance of Air Conditioners
1. Voltage Range for Air Conditioners:
- Fixed-Speed Air Conditioners**: Voltage range of 198-242V.
- Inverter Air Conditioners**: Voltage range of 187-242V, capable of ultra-low voltage startup at 150V.
2. Simple Fault Detection for Air Conditioners:
- Check if the power supply is working and whether the voltage is within the normal range.
- Check if the remote control batteries have power.
- Verify if the set parameters are correct.
- Ensure there is no electromagnetic interference near the indoor unit, which might affect the remote control signal.
3. Determining Cooling Capacity of Air Conditioners:
- For a standard room with a ceiling height of 2.7 meters, ceiling height of 2.4 meters, and window area of 1.8 meters * 1.8 meters, with insulation measures and good sealing, the cooling load per square meter is 130W. However, due to factors such as city, orientation, and floor level, general customers can estimate it at 160W/square meter.
4. Selection Requirements for Air Conditioner Sockets:
- Generally, wall-mounted units and cabinet units below 2P require a 10-16A socket.
- Cabinet units above 2P require a 25-30A socket, with reliable grounding and located close to the air conditioner plug.
- Air conditioners must use a dedicated fixed socket, and no other appliances should be connected to the socket.

5. Power Supply Wiring Requirements for Air Conditioners:
- The main power line should not be less than 10 square millimeters.
- The air conditioner should have a dedicated branch circuit with a capacity of at least 1.5 times the maximum current of the air conditioner.
- (For units below 2P, 2.5-4 square millimeters of single-core copper wire should be used, and for units above 2P, 6 square millimeters of single-core copper wire should be used.)